The UNICOMM interface modules are able to establish communication line between HART-capable field devices and process controller computer. The communication line can be USB or RS485. The UNICOMM HART modems are applicable not only for NIVELCO transmitters, but for all HART-capable transmitters which use standard HART communication. The device is galvanically isolated from both (USB and HART) sides, when it is used as a HART-USB modem, connected into the USB input of a PC, the modem does not need external power supply. The UNICOMM SAK-305 modules can be connected into a suitable device with RS485 interface input, used as a HART-RS485 modem. The communication protocol is HART on the RS485 line. In this case the device needs external power supply. The Ex versions can be connected to transmitters placed in hazardous areas
Operating Principle:
Communication ModuleFeatures:
- Transferring measurement data to PC
- Connecting field transmitters to the USB or RS485 input of a PC
- DIN rail mountable or KLEPS2 connector version
- No need for power supply when USB output is used
- Galvanic isolation
- Ex version
Application:
- Communication interface (modem) between HART-capable transmitters and PC
- Minimal system configuration: o free USB port o Windows XP operation system
Specification:
- Input: HART
- Output: USB / RS485 (HART over RS485)
- Power supply: Supplied from USB port / 24V DC (10-30 V) nominal voltage
- Connection to the HART line: KLEPS 2 / Terminal
- Connection to PC: USB 1.1 ”B” socket / Terminal
- Ambient temperature: -13 °F .. +158 °F
- Ingress Protection: IP 20
- Ex marking: ATEX Ex II (1) G [Ex ia Ga] IIC